Skip to content

Language

SKU RLY08/A

8 channels relay module

Original price €52,13 - Original price €52,13
Original price
€52,13
€52,13 - €52,13
Current price €52,13

All prices are VAT included

Availability:
Out of stock
Availability:
On order
Shipping: 1 day
Request Quantity Discount and Information

Number of Relay's

-

8
Power - 5v @ 100mA max.
Control interface - Serial or I2C
Relay current - Up to 1Amp @30vdc or 60vac. 500mA@110vac. 250mA@250vac
Connections - Screw Terminals for N/ON/C and Common contacts.
Expansion - Up to 8 modules on Serial or I2C bus

I2C MODE:

Connections

I2C Mode selection
I2C operation is activated when the mode pin is left open circuit.


I2C Operations
I2C Bus
The RLY08 is located on the I2C bus at a factory default address of 0X70. The SCL and SDA lines should have pull-up resistors on them somewhere on the bus. You only require 1 pair of resistors for the whole I2C bus, not specifically for the RLY08. They are normally on the master controller and you may already have them. If not, anything between 1k8 and 10k should work. I recommend 1k8 for best noise immunity.

RLY08 register set
The RLY08 has only two registers, register 0 and acts as a dual purpose register. When written to it is the command register where all of the instructions from the commands section should be sent. When read it returns the software version.
Register 1 is the relay register, when written to it allows the user to change all eight relay positions at once with a single byte. When the register is read it provides the current positions of the relays. If all relays are powered the register would contain 255 (1111 1111), all relays in the un-powered state would result in 0 (0000 0000)

I2C register set

register

Read

Write
0 Software version Command register
1 Relay states Relay states

Commands for I2C

decimal hex

command

100 0x64 All relays on
101 0x65 Turn relay 1 on
102 0x66 Turn relay 2 on
103 0x67 Turn relay 3 on
104 0x68 Turn relay 4 on
105 0x69 Turn relay 5 on
106 0x6A Turn relay 6 on
107 0x6B Turn relay 7 on
108 0x6C Turn relay 8 on
110 0x6E All relays off
111 0x6F Turn relay 1 off
112 0x70 Turn relay 2 off
113 0x71 Turn relay 3 off
114 0x72 Turn relay 4 off
115 0x73 Turn relay 5 off
116 0x74 Turn relay 6 off
117 0x75 Turn relay 7 off
118 0x76 Turn relay 8 off

Changing the RLY08 Address
To change the I2C address of the RLY08 you must have only one module on the bus. Write the 3 sequence commands in the correct order followed by the address. Example; to change the address of a RLY08 currently at 0x70 (the default shipped address) to 0x7A, write the following to address 0x70; (0xA0, 0xAA, 0xA5, 0x7A ). These commands must be sent in the correct sequence to change the I2C address, additionally, No other command may be issued in the middle of the sequence. The sequence must be sent to the command register at location 0, which means 4 separate write transactions on the I2C bus. When done, you should label the module with its address, however if you do forget, just power it up without sending any commands. The RLY08 will flash its address out on the LED. One long flash followed by a number of shorter flashes indicating its address. The flashing is terminated immediately on sending a command to the RLY08 and then becomes a power LED.

Address Long Flash Short flashes
Decimal Hex
112 0x70 1 0
114 0x72 1 1
116 0x74 1 2
118 0x76 1 3
120 0x78 1 4
122 0x7A 1 5
124 0x7C 1 6
126 0x7E 1 7

Take care not to set more than one module to the same address, there will be a bus collision and very unpredictable results.

SERIAL MODE:

Connections

Serial mode selection
Serial Mode is selected by connecting the Mode pin to ground. The Tx pin is out of the RLY08 and should be connected to Rx on your controller. The Rx pin is into the RLY08 and should be connected to Tx on your controller. These signals are 5v levels, not RS232. Do NOT connect RS232 directly to the module - you will destroy it. Use a MAX232 or equivalent to convert the RS232 levels to 5v.

Communication settings
The Serial mode operates over a link with a baud rate of 9600 bps (no parity, 1 stop bit) and 5v signals, The RLY08 can be found at a factory default address of 1, although this is easily changed to another of eight locations - see Changing the RLY08 Address .

Commands
To send a command to the RLY08, you need to send two bytes. The first is the RLY08's address 1 (default) to 8, and then the actual command itself - see below. The RLY08 will then carry out the command and if applicable send its response. The only exception to this being the "Set relay states" command, it requires an additional required states byte to be sent immediately after the command byte. This will then set all relays to the status of the equivalent bit within the byte, with a high bit powering the relay on and a low bit turning it off.

Commands for Serial

Command

Action

dec hex
90 5A Get software version - transmits a single byte back to the controller containing the software revision
91 5B

Get relay states - transmits a single byte back to the controller, bit high meaning the corresponding relay is powered

ninety two 5C Set relay states - the next byte sent to the command register will set all relay states, All on = 255 (11111111) All off = 0
100 64 All relays on
101 65 Turn relay 1 on
102 66 Turn relay 2 on
103 67 Turn relay 3 on
104 68 Turn relay 4 on
105 69 Turn relay 5 on
106 6A Turn relay 6 on
107 6B Turn relay 7 on
108 6C Turn relay 8 on
110 6E All relays off
111 6F Turn relay 1 off
112 70 Turn relay 2 off
113 71 Turn relay 3 off
114 72 Turn relay 4 off
115 73 Turn relay 5 off
116 74 Turn relay 6 off
117 75 Turn relay 7 off
118 76 Turn relay 8 off
160 A0 1st byte in sequence to change serial address
165 A5 3rd byte in sequence to change serial address
170 AA 2nd byte in sequence to change serial address

Changing the RLY08 Address
To change the address of the RLY08 you must have only one module connected. Write the 3 sequence commands in the correct order followed by the address. For example; to change the address of a RLY08 currently at 1 (the default shipped address) to 5, write the following to address 1; (0xA0, 0xAA, 0xA5, 0x05 ). These commands must be sent in the correct sequence to change the address, additionally, No other command may be issued in the middle of the sequence. The sequence must be sent as four separate commands to the current address of the module. i.e. 0x01, 0xA0 then 0x01, 0xAA, then 0x01, 0xA5 and finally 0x01, 0x05. When done, you should label the module with its new address, however if you do forget, just power it up without sending any commands. The RLY08 will flash its address out on the LED. One long flash followed by a number of shorter flashes indicating its address. The flashing is terminated immediately on sending a command the RLY08.

Address Long Flash Short flashes
Decimal Hex
1 01 1 0
2 02 1 1
3 03 1 2
4 04 1 3
5 05 1 4
6 06 1 5
7 07 1 6
8 08 1 7

Take care not to set more than one module to the same address, there will be a bus collision and very unpredictable results.